d1xc1x05rac230bn1a1r-r-den-coi-radial-alarm-horn-xenon-strobe-e2s.png

Model: D1XC1X05RAC230BN1A1R/R Đèn còi Radial Alarm Horn & Xenon Strobe E2S

Alarm Horn:

 

Maximum output:

Class I version: 115dB(A) @ 1 metre [106dB(A) @ 10ft/3m]
Class II version: 96dB(A) @ 1 metre [87dB(A) @ 10ft/3m]

Nominal output:

Class I version: 110dB(A) @ 1m +/- 3dB – Tone 4 [101dB(A) @ 10ft/3m]
Class II version: 91dB(A) @ 1 metre [82dB(A) @ 10ft/3m]

No. of tones:

64 (UKOOA / PFEER compliant)

No. of stages:

4

Volume control:

Adjustable -12dB(A)

Effective range:

125m/410ft @ 1KHz

Supply Voltages:

24Vdc; 115Vac; 230Vac

Stage switching:

DC units: negative or positive
AC units: common supply line

Strobe Beacon:

 

Energy:

5 Joules (5Ws)

Flash rates:

Option 1: 1Hz (60 fpm)
Option 2: 1.5Hz (90 fpm)
Option 3: Double Strike

Peak Candela:

500,000 cd – calculated from energy (J)

Effective Intensity:

250 cd – calculated from energy (J)

Peak Candela:

46,976 cd* – measured ref. to I.E.S.

Effective Intensity:

143 cd* – measured ref. to I.E.S.

Lens colours:

Amber, Blue, Clear, Green, Magenta, Red & Yellow

Tube life :

Emissions reduced to 70% > 5 million flashes

General:

 

Ingress protection:

EN60529: IP66
UL50E / NEMA250: 4 / 4X / 3R / 13

Enclosure material:

Marine grade aluminium LM6- copper free
Chromated & powder coated – corrosion proof

Colour:

Red (RAL3000), Grey (RAL7038)

Cable entries:

1 × 1/2"NPT & 2 x M20 x 1.5mm
1 × 1/2"NPT & 2 × 1/2"NPT
1 × 1/2"NPT & 2 × 3/4"NPT

Terminals:

0.5 – 2.5mm² (20-14 AWG)

Grounding stud:

M5

Operating temp:

24Vdc & 115Vac: -40° to +70°C [-40° to +158°F]
230Vac: -40° to +55°C [-40° to +131°F]

Storage temp:

-50° to +70°C [-58° to +158°F]

Relative humidity:

95% – Additional tropicalisation is recommended for applications where both high relative humidity and high ambient temperatures exist